''RM6-2,IIII,MANUAL&ENCLOSURE,DOWN VENTING DOWN VENTING RMU,11KV,630A,M/GRM6-2,MOUNTED INSIDE RA6998 OUTDOORENCLOSURE,25KA FOR 1SEC,IAC CLASS A-FLR 20KA/1SEC, IIII, SF6 RING MAINUNIT SWITCHGEAR CONFIGURATION (LS1,LS2,LS3,LS4), COMPLETE WITH THEFOLLOWING ITEMS:-RA6998 OUTDOOR ENCLOSURE-FLAIR22D FAULT INDICATORS ON ALL UNITS (LS1,LS2,LS3,LS4) WITH THERELVANT CTS.-ARC CONTAINMENTS COVERS ON (LS1,LS2,LS3,LS4).-INTERLOCKED CABLE COVERS WITH EARTH SWITCH ON (LS1,LS2,LS3,LS4)- VPIS-VO ON (LS1,LS2,LS3,LS4)-DOWNWARD ARC SHUTE-SA POWER NETWORK LABELS IN ACCORDANCE WITH SPEC QT2026MAX LOAD RATINGS:LS = 630ADOWNWARD VENTING UNIT''
Sign up to our newsletter to recieve the latest offers, product news & discounts.